按照问题的建议(TwinCAT 3.0 Automation Interface without Visual Studio?),我收到1793错误(服务器不支持该服务)。
我尝试使用Twincat3编写程序来启动/重新启动/配置Beckhoff PLC(这与小型Beckhoff GUI应用程序具有相同的功能)。我试图遵循上述解决方案的建议,但似乎无法设置状态。从设备读取值的工作原理:
nPort = AdsPortOpen();
nErr = AdsGetLocalAddress(pAddr);
if (nErr)
cerr << "Error: AdsGetLocalAddress: " << nErr << '\n';
// TwinCAT 3 PLC1 = 851
pAddr->port = 10000;// 10000 as advised @ stackoverflow;
cout << "(R) -> PLC Run\n";
cout << "(S) -> PLC Stop\n";
cout.flush();
ch = _getch();
ch = toupper(ch);
while ((ch == 'R') || (ch == 'S'))
{
switch (ch)
{
case 'R':
nAdsState = ADSSTATE_RUN;
break;
case 'S':
nAdsState = ADSSTATE_CONFIG;
break;
}
nErr = AdsSyncReadStateReq(pAddr, &nAdsState, &nDeviceState);// , 0, pData);
if (nErr) cerr << "Error: AdsSyncReadStateReq: " << nErr << '\n';
cout << nAdsState << " " << nDeviceState << endl;
nErr = AdsSyncWriteControlReq(pAddr, nAdsState, nDeviceState, 0, pData);
if (nErr) cerr << "Error: AdsSyncWriteControlReq: " << nErr << '\n'; //1793
ch = _getch();
ch = toupper(ch);
}
答案 0 :(得分:1)
好的,我找到了解决方案,也许有人会觉得有用。上面的代码中没有错误,但必需的AdsState错误。看来ADSSTATE_RUN和ADSSTATE_CONFIG(以及此枚举中的其他一些)仅用于返回状态。
要实际更改设备状态,应使用 ADSSTATE_RESET 和 ADSSTATE_RECONFIG (这两个值反映了在运行模式和配置模式下启动/重新启动的功能)。同样,通过ADSSTATE_STOP,您可以完全停止PLC,而ADSSTATE_SHUTDOWN允许重新启动或关闭PC(取决于DeviceState值0/1)。