我想用允许smart meter的PC进行通信,以允许Modbus TCP通信,该PC将成为主机,我只需要读取保持寄存器并以浮点格式显示它们即可。我在pymodbus 2.2.0中使用python,我的代码是:
from pymodbus.client.sync import ModbusTcpClient
client = ModbusTcpClient('169.254.00.10')
result = client.read_holding_registers(1845,1,unit=0x01)
print('**************************************************************')
print(result)
client.close()
我得到的是:
DEBUG:pymodbus.transaction:Current transaction state - IDLE
DEBUG:pymodbus.transaction:Running transaction 1
DEBUG:pymodbus.transaction:SEND: 0x0 0x1 0x0 0x0 0x0 0x6 0x1 0x3 0x7 0x35 0x0 0x1
DEBUG:pymodbus.client.sync:New Transaction state 'SENDING'
DEBUG:pymodbus.transaction:Changing transaction state from 'SENDING' to 'WAITING FOR REPLY'
DEBUG:pymodbus.transaction:Changing transaction state from 'WAITING FOR REPLY' to 'PROCESSING REPLY'
DEBUG:pymodbus.transaction:RECV: 0x0 0x1 0x0 0x0 0x0 0x5 0x1 0x3 0x2 0x6 0xc
DEBUG:pymodbus.framer.socket_framer:Processing: 0x0 0x1 0x0 0x0 0x0 0x5 0x1 0x3 0x2 0x6 0xc
DEBUG:pymodbus.factory:Factory Response[ReadHoldingRegistersResponse: 3]
DEBUG:pymodbus.transaction:Adding transaction 1
DEBUG:pymodbus.transaction:Getting transaction 1
DEBUG:pymodbus.transaction:Changing transaction state from 'PROCESSING REPLY' to 'TRANSACTION_COMPLETE'
**************************************************************
ReadRegisterResponse (1)
您知道如何使用pymodbus 2.2.0解决该问题吗?
答案 0 :(得分:0)
您必须从响应中提取寄存器,请尝试以下操作:
print(result.registers)
或者,如果您希望它们一个一:
for reg in result:
print(reg)
如果不确定服务器是否正在运行,其IP或端口是否在运行,则最好使用独立工具进行测试;如果您使用的是Windows,则可以使用QModMaster来确保设置和映射。
请注意,仅使用一个Modbus寄存器就无法获得浮点数,因为Modbus寄存器是16位整数。如果要浮动,则需要读取两个寄存器。
另一方面,如果您只想验证客户端代码,则可以与客户端代码同时在计算机上运行this example。当然,您必须将脚本上的IP地址更改为localhost
,将端口更改为5020
,并将要读取的寄存器号更改为较小的数字(或增加服务器数据存储区的大小) 。如果您使用的是Windows,则可能需要在防火墙上禁用或创建规则。