(这里最好是新手Python程序员。)
我使用一个模块来访问名为BAC0的楼宇自动化系统。该脚本运行Windows笔记本电脑后,便通过本地Wifi LAN将BACnet与建筑物自动化系统进行通信,从而从建筑物中创建建筑物自动化设备。
具体来说,下面的脚本是每120秒对热水设备控制器轮询一次离开温度传感器,然后在while True循环中每600秒更新一次。
import BAC0
import time
#alarm setpoint
setPoint = 140
#connect to device
bacnet = BAC0.lite()
hws = BAC0.device('100:99', 30099, bacnet, poll=120, history_size=10000)
while True:
data = hws['SHWS-T']
time.sleep(600)
if data > setPoint:
good = f'[INFO] - Looks good, the temp of the {data} on {time.ctime()}'
print(good)
else:
bad = f'[INFO] - Looks bad, the temp of the {data} on {time.ctime()}'
print(bad)
print("Here's the coldest last 10 recorded boiler supply temp readings")
print(data.history.nsmallest(n=10, keep='last'))
print("I better get some help!")
无论如何,每隔一段时间会发生一次,控制器没有响应,然后脚本停止的原因是,如果这……如果我知道如何进行重试retry
,那就太好了3次,然后pass
再等待600秒以重试...
我知道这在下面是不正确的,但类似这样的东西?
try:
if isinstance(Exception: Problem reading : SHWS-T)
# retry function?
retry()
else:
# This is our sensor value
pass
完整追溯:
benbartling@benbartling-HP-ProDesk-600-G1-SFF ~/Desktop/bac0 $ python interpreter.py
2019-04-12 13:39:49,484 - INFO | Starting BAC0 version 0.99.944 (Lite)
2019-04-12 13:39:49,513 - INFO | Using ip : 10.30.4.200
2019-04-12 13:39:49,514 - INFO | Starting app...
2019-04-12 13:39:49,514 - INFO | BAC0 started
2019-04-12 13:39:49,514 - INFO | Registered as Simple BACnet/IP App
2019-04-12 13:39:51,517 - INFO | Changing device state to DeviceDisconnected'>
2019-04-12 13:39:57,867 - INFO | Changing device state to RPMDeviceConnected'>
2019-04-12 13:39:58,306 - INFO | Device 30099:[Boiler] found... building points list
2019-04-12 13:39:59,683 - INFO | Ready!
2019-04-12 13:39:59,688 - INFO | Polling started, values read every 120 seconds
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.62 degreesFahrenheit on Fri Apr 12 13:50:05 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.78 degreesFahrenheit on Fri Apr 12 14:00:06 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 143.18 degreesFahrenheit on Fri Apr 12 14:10:06 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.33 degreesFahrenheit on Fri Apr 12 14:20:06 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 143.15 degreesFahrenheit on Fri Apr 12 14:30:07 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.97 degreesFahrenheit on Fri Apr 12 14:40:07 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.42 degreesFahrenheit on Fri Apr 12 14:50:07 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.96 degreesFahrenheit on Fri Apr 12 15:00:08 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.19 degreesFahrenheit on Fri Apr 12 15:10:08 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.51 degreesFahrenheit on Fri Apr 12 15:20:09 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 142.76 degreesFahrenheit on Fri Apr 12 15:30:15 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 142.10 degreesFahrenheit on Fri Apr 12 15:40:15 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 142.66 degreesFahrenheit on Fri Apr 12 15:50:16 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 142.86 degreesFahrenheit on Fri Apr 12 16:00:16 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.98 degreesFahrenheit on Fri Apr 12 16:10:16 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 141.67 degreesFahrenheit on Fri Apr 12 16:20:16 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 142.45 degreesFahrenheit on Fri Apr 12 16:30:17 2019
[INFO] - Looks good, the temp of the Boiler/SHWS-T : 143.06 degreesFahrenheit on Fri Apr 12 16:40:17 2019
Traceback (most recent call last):
File "/home/benbartling/anaconda3/lib/python3.6/site-packages/BAC0/core/devices/Points.py", line 112, in value
self.properties.device.properties.address, self.properties.type, str(self.properties.address)))
File "/home/benbartling/anaconda3/lib/python3.6/site-packages/BAC0/core/io/Read.py", line 163, in read
"APDU Abort Reason : {}".format(reason))
BAC0.core.io.IOExceptions.NoResponseFromController: APDU Abort Reason : noResponse
During handling of the above exception, another exception occurred:
Traceback (most recent call last):
File "interpreter.py", line 20, in <module>
if data > setPoint:
File "/home/benbartling/anaconda3/lib/python3.6/site-packages/BAC0/core/devices/Points.py", line 524, in __gt__
return self.value > other
File "/home/benbartling/anaconda3/lib/python3.6/site-packages/BAC0/core/devices/Points.py", line 116, in value
'Problem reading : {}'.format(self.properties.name))
Exception: Problem reading : SHWS-T
答案 0 :(得分:0)
您可以尝试使用重试的PyPi软件包,并根据需要修改程序。 选中https://pypi.org/project/retrying/
遵循这些原则。
@retry(stop_max_attempt_number=3)
def read_from_sensor():
#your code here
pass
@retry(wait_fixed=6000)
def get_sensor_reading():
read_from_sensor()
答案 1 :(得分:0)
在定义轮询时,您无需阅读逻辑中的要点。尝试使用“ hws [SHWS-T] .lastValue”
使用该点的呼叫将强制在网络上进行读取,效率不高。 LastValue将使用该点的历史记录。