我正在开发一个C#自定义OPC客户端,我开始在控制台应用程序中快速编写,一切都按照我的要求完美运行。
然后我决定制作一个Windows窗体应用程序以获得视觉体验。
Windows窗体应用程序只是停止工作,大约一分钟后停止从OPC服务器读取数据。控制台应用程序在哪里继续阅读和阅读。
我在调试模式中找不到任何明显的东西。
我绝对抓着稻草,希望有人能说清楚。
每个应用程序都使用OPCFoundation提供的.dll文件。
以下是控制台应用
static void Main(string[] args)
{
Opc.URL url = new Opc.URL("opcda://localhost/RSLinx OPC Server");
Opc.Da.Server server = null;
OpcCom.Factory fact = new OpcCom.Factory();
server = new Opc.Da.Server(fact, null);
server.Connect(url, new Opc.ConnectData(new System.Net.NetworkCredential()));
// Create a group
Opc.Da.Subscription group;
Opc.Da.SubscriptionState groupState = new Opc.Da.SubscriptionState();
groupState.Name = "Group";
groupState.Active = true;
group = (Opc.Da.Subscription)server.CreateSubscription(groupState);
// add items to the group.
Opc.Da.Item[] items = new Opc.Da.Item[6];
items[0] = new Opc.Da.Item();
items[0].ItemName = "[UX1]F20:9";
items[1] = new Opc.Da.Item();
items[1].ItemName = "[UX1]F22:30";
items[2] = new Opc.Da.Item();
items[2].ItemName = "[UX1]F22:6";
items[3] = new Opc.Da.Item();
items[3].ItemName = "[UX1]F18:8";
items[4] = new Opc.Da.Item();
items[4].ItemName = "[UX1]F22:32";
items[5] = new Opc.Da.Item();
items[5].ItemName = "[UX1]F22:5";
items = group.AddItems(items);
group.DataChanged += new Opc.Da.DataChangedEventHandler(OnTransactionCompleted);
}
static void OnTransactionCompleted(object group, object hReq, Opc.Da.ItemValueResult[] items)
{
Console.WriteLine("------------------->");
Console.WriteLine("DataChanged ...");
for (int i = 0; i < items.GetLength(0); i++)
{
Console.WriteLine("Item DataChange - ItemId: {0}", items[i].ItemName);
Console.WriteLine(" Value: {0,-20}", items[i].Value);
Console.WriteLine(" TimeStamp: {0:00}:{1:00}:{2:00}.{3:000}",
items[i].Timestamp.Hour,
items[i].Timestamp.Minute,
items[i].Timestamp.Second,
items[i].Timestamp.Millisecond);
}
Console.WriteLine("-------------------<");
}
这是WinForm应用程序
public Form1()
{
InitializeComponent();
_Form1 = this;
}
public static Form1 _Form1;
public void update(string message)
{
this.richTextBox1.Text = message;
}
private void Form1_Load(object sender, EventArgs e)
{
readplc();
}
static void readplc()
{
Opc.URL url = new Opc.URL("opcda://localhost/RSLinx OPC Server");
Opc.Da.Server server = null;
OpcCom.Factory fact = new OpcCom.Factory();
server = new Opc.Da.Server(fact, null);
server.Connect(url, new Opc.ConnectData(new System.Net.NetworkCredential()));
// Create a group
Opc.Da.Subscription group;
Opc.Da.SubscriptionState groupState = new Opc.Da.SubscriptionState();
groupState.Name = "Group";
groupState.Active = true;
group = (Opc.Da.Subscription)server.CreateSubscription(groupState);
// add items to the group.
Opc.Da.Item[] items = new Opc.Da.Item[6];
items[0] = new Opc.Da.Item();
items[0].ItemName = "[UX1]F20:9";
items[1] = new Opc.Da.Item();
items[1].ItemName = "[UX1]F22:30";
items[2] = new Opc.Da.Item();
items[2].ItemName = "[UX1]F22:6";
items[3] = new Opc.Da.Item();
items[3].ItemName = "[UX1]F18:8";
items[4] = new Opc.Da.Item();
items[4].ItemName = "[UX1]F22:32";
items[5] = new Opc.Da.Item();
items[5].ItemName = "[UX1]F22:5";
items = group.AddItems(items);
group.DataChanged += new Opc.Da.DataChangedEventHandler(OnTransactionCompleted);
}
static void OnTransactionCompleted(object group, object hReq, Opc.Da.ItemValueResult[] items)
{
for (int i = 0; i < items.GetLength(0); i++)
{
UIUpdater TEXT = new UIUpdater();
TEXT.UpdateText(items.GetLength(0).ToString() + " t " + i.ToString() + "Item DataChange - ItemId:" + items[i].ItemName +
"Value: " + items[i].Value + " TimeStamp: " + items[i].Timestamp.Hour + ":" +
items[i].Timestamp.Minute + ":" + items[i].Timestamp.Second + ":" + items[i].Timestamp.Millisecond);
}
}
UIUpdate类
class UIUpdater
{
public void UpdateText(string DATA)
{
Form1._Form1.update(DATA);
}
public class UpdateUI
{
public int updatedRows { get; set; }
public string Custom1 { get; set; }
public string Custom2 { get; set; }
public string Custom3 { get; set; }
public string exception { get; set; }
public plcTextStatus PLCStatus { get; set; }
}
有任何问题请咨询!
答案 0 :(得分:5)
如所怀疑的,这是一个跨线程问题。问题是您无法从UI线程以外的任何其他线程更新UI。事务完成的事件实际上是在一个单独的线程上调用的,因此它更新了UI。
它可以工作一段时间,因为它相对容忍错误,但是你可能已达到一个点,即你正在死锁或抛出一个未被捕获(或报告)的异常。
虽然修复很简单。
在这种方法中:
public void update(string message)
{
this.richTextBox1.Text = message;
}
将其更改为:
public void update(string message)
{
richTextBox1.Invoke(
(MethodInvoker) delegate
{
richTextBox1.Text = message;
});
}
这样做是告诉richTextBox1
“调用”或在其拥有的线程(也称为UI线程)上运行以下委托(函数)。
您应该尽量避免在此代码中使用static
方法和引用。我认为你所拥有的代码不应该是实例方法而不是静态方法。
正如旁注,我编写了OPC程序,每秒处理数千个标签和数百个UI更新 。你正在做什么适用于小型演示程序,但不会很好地扩展。当架构增长时,您需要开始批量处理UI更新,这样您就不会在更新内部重复调用UI线程。
修改强>
您遇到的另一个问题是使用本地引用(例如OPC服务器和订阅)并演示内存泄漏和僵尸对象。发生的事情是readplc
方法超出范围,并且您已创建对内部对象的引用。由于您无法取消订阅该事件,因此该事件会继续触发。这些变量应在readplc
方法的范围之外声明,以便您可以正确取消订阅事件并关闭OPC服务器。否则你将离开zombie订阅(查看RSLinx OPC Diagnostics页面,你会看到你所有的订阅都在那里)。
答案 1 :(得分:0)
将您的服务器作为表单级对象放在readplc()方法的外部。 只要您的表单被实例化(未关闭) - 您的服务器对象将处于活动状态,您的订阅事件也应如此。
服务器很可能是由垃圾收集器收集的。