是Modbus的新手,使用Modbus RTU开发应用程序。我想知道如何找出RTU消息帧分离时间。在Modbus RTU规范中,它提到了3.5个字符时间,但没有更多关于我如何决定这个间隔的数据。和wat是计算分离时间的步骤吗?
答案 0 :(得分:11)
查看Modbus Serial Line Protocol and Implementation Guide V1.02
的第13页在底部,您将找到解释字符间超时(t1.5)和帧间延迟(t3.5)值的注释。
对于超过19200的波特率,固定值。对于较慢的波特率,需要计算它们(从Arduino的SimpleModbusMaster库中提取):
// Modbus states that a baud rate higher than 19200 must use a fixed 750 us
// for inter character time out and 1.75 ms for a frame delay.
// For baud rates below 19200 the timeing is more critical and has to be calculated.
// E.g. 9600 baud in a 10 bit packet is 960 characters per second
// In milliseconds this will be 960characters per 1000ms. So for 1 character
// 1000ms/960characters is 1.04167ms per character and finaly modbus states an
// intercharacter must be 1.5T or 1.5 times longer than a normal character and thus
// 1.5T = 1.04167ms * 1.5 = 1.5625ms. A frame delay is 3.5T.
if (baud > 19200)
{
T1_5 = 750;
T3_5 = 1750;
}
else
{
T1_5 = 15000000/baud;
T3_5 = 35000000/baud;
}
答案 1 :(得分:1)
Modbus RTU使用11位字符,无论是否使用奇偶校验。对于一个字符时间,公式应为:11 * 1000000 /(baud_rate),这适用于波特率< = 19200 bps。对于波特率>使用固定时间为19200 bps,3.5 char时间为1750微秒,1.5 char时间为750微秒